Commissioning Ipc6325 Cameras - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
4.
Step 2 Enabling camera NTP synchronization.
The camera NTP synchronization function for the server is disabled by default. The camera
NTP synchronization function needs to be enabled for the server that connects to cameras.
After the camera NTP synchronization function is enabled, cameras will automatically
time-synchronize from their access servers.
1.
2.
3.
4.
5.
----End

5.11.2 Commissioning IPC6325 Cameras

Prerequisites
For details about how to commission IP cameras and set parameters for them, see the
document delivered or click
Issue 06 (2020-01-02)
Set Business IP to 192.168.11.110, Subnet mask to 255.255.255.0, Gateway IP to 192.168.11.1.
The values here are examples. The actual values prevail.
Set NAT IP to VCN500 external IP address, which is the same as the external IP address mapped
from the VCN500 internal IP address displayed on the ECC800.
Configure the NTP synchronization. After setting The NTP clock source server to Yes,
set the IP address of the NTP server.
The server that connects to cameras needs to enable the camera NTP synchronization function. For the
detailed operations, see
Step
Log in to the OMU portal of the VCN as the Admin user.
Choose Maintenance > Unified Configuration.
Select the server that the camera needs to access, set Module name to SCU and
Parameter type to System property, and click Search.
Figure 5-21 Configuring Camera NTP Synchronization
In the search results, click Edit in the row where Parameter Name is NTPIPC and set
Value to 1.
Click Save. After the camera NTP synchronization function is enabled, the camera, after
being connected to the server, will automatically time-synchronize with the server.