Huawei ECC800 User Manual page 178

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Step 4 (Optional) If PUE function is set to Disable, select Enable from the drop-down list box and
click Submit.
Step 5 Set the PUE configuration mode to Standard, and click Submit.
Step 6 View the PUE. Choose Query > Performance Data and set Device to ECC800 from the
drop-down list box. For other searching criteria such as Performance data, Statistical
period, Start time, and End time, select the item based on requirements and click Query.
You can also view the PUE in the dashboard or curve on the home page.
----End
Example of PUE Calculation
This section describes how to calculate PUE for the integrated UPS cabinet connected.
1.
2.
3.
Issue 06 (2020-01-02)
Export performance data.
a.
Log in to the ECC800 WebUI as an administrator.
b.
Choose Query > Export Data.
c.
(Optional) Select Encryption password and enter an encryption password.
Record the password for decompressing the data package.
d.
Set Data type to Performance data from the drop-down list box and click Export
Historical Data.
Performance data source: The ECC800 obtains total electricity energy from the power distribution
devices.
e.
Select a path to save the exported data to the PC.
Filter performance data of the integrated UPS.
a.
Decompress the performance data package and open the perfmg_1_hour.csv file.
In this example, the statistical period of the performance data is 1 hour.
The statistical period of the exported performance data can be 1 minute, 5 minutes, 15 minutes, 30
minutes, 1 hour, one day, one week, one month, and one year.
b.
Select Integrated UPS Cabinet 1 for Equipment, and select IT equipment
output total valid energy as well as Total active electricity energy of UPS input
for Performance Data.
Calculate the PUE of the smart module.
a.
Calculate increment in the total active electricity energy of the IT load output and
increment in the total active electricity energy of the UPS input.
In this example, the start time is 18:00 and the end time is 19:00.
Increment in the total active electricity energy of the IT load output = 104665.1 kWh – 104648.7
kWh = 16.4 kWh; increment in the total active electricity energy of the UPS input = 170600.3 kWh
– 170572.6 kWh = 27.7 kWh.
Copyright © Huawei Technologies Co., Ltd.