Component Replacement; Replacing An Ecc800 Main Control Module - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual

8.3 Component Replacement

1.
2.
3.
4.

8.3.1 Replacing an ECC800 Main Control Module

Prerequisites
Procedure
Step 1 Use the Back Up Current Settings function to record the ECC800 configuration information
or manually record the information.
Path: Maintenance > Configuration File > Back Up Current Settings
Step 2 Label each cable and antenna based on the corresponding ports on the ECC800 main control
module.
Step 3 Remove cables, the WiFi module, and antennas from the ECC800 main control module.
Step 4 Loosen the screws on both sides of the ECC800 main control module and pull the handles on
both sides of the ECC800 main control module to remove the main control module.
Issue 06 (2020-01-02)
For southbound devices that requires parameter synchronization, such as CIM and T/H sensor, select the
device from the device type drop-down list box.
After replacing components, log in to the WebUI and choose Maintenance >
Parameter Sync to access the parameter synchronization page.
Click Device type and select the component type from the drop-down list.
Select the failure device in Source Device, select the reserved device in Target Device,
and click Submit to synchronize the configuration parameters of the failure device to the
reserved device.
On the Monitoring > System > ECC800 > Controls > Delete device with
communication failure tab page, delete the failure device that fails in communication
and add the reserved device to the smart module view.
The ECC800 main control module is hot-swappable.
Before disconnecting cables from the ECC800 main control module, label the cables based
on the corresponding ports.
Tools: ESD wrist strap, ESD gloves, Phillips screwdriver, labels, marker
Materials: a new undamaged and undeformed ECC800 main control module of the
appropriate model