How To Set Parameters For Alarm Enable, Severity, And Loudspeaker; How Can I View Real-Time Monitoring Data, Active Alarms, Historical Alarms, Access Event, And Operation Logs - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Step 4 In the displayed The WebUI will exit or not respond after the new IP address is set. You
need to log in again with the new IP address. Do you want to change the IP address?
dialog box, click OK.
----End
9.1.4 How to Set Parameters for Alarm Enable, Severity, and
Loudspeaker?
Context
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose System Settings > Alarm Parameters.
Step 3 Select ECC800 from the drop-down list box and click Confirm.
Step 4 Set Operation log full to Enable or Disable under Enable Alarm as required. Set Severity
to Critical, Major, Minor, or Warning as required. Set Loudspeaker to Enable or Disable
as required.
Step 5 Click Submit.
9.1.5 How Can I View Real-Time Monitoring Data, Active Alarms,
Historical Alarms, Access Event, and Operation Logs?
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Click Monitoring, select the device to be viewed, and select Running Info to view the
real-time data of the device.
Step 3 Choose Home > Active Alarms to view the active alarms of the ECC800. Click Details in
the Alarm Details area to view alarm details of devices.
Step 4 Choose Query to view the historical alarms, access events and operation logs of the devices.
1.
2.
3.
----End
Issue 06 (2020-01-02)
You can set parameters under Enable Alarm, Severity, and Loudspeaker based on
requirements. When an alarm is set to Disable, the ECC800 will not report this alarm. If
an alarm is associated with the loudspeaker and Loudspeaker is set to Enable, the
loudspeaker produces sound when the alarm is generated.
The setting methods for different alarms are the same. This section describes how to set
the Operation log full alarm for ECC800.
To view historical alarms, choose Query > Historical Alarms, set Device, Start time,
End time, and Sort mode, and click Query.
To view access events, choose Query > Access Event.
To view operation logs, choose Query > Operation Log.
Copyright © Huawei Technologies Co., Ltd.
9 FAQ
186