7.6.2 Setting and Adding an Infrared Remote Control Module

Prerequisites
Context
If an infrared remote control module is replaced, you need to add the infrared remote control
module to the ECC800 WebUI.
Procedure
Step 1 Set monitoring parameters for the infrared remote control module.
1.
Table 7-2 Setting a device address
Address
1
2
Step 2 Add an infrared remote control module.
1.
2.
3.
Issue 06 (2020-01-02)
The infrared remote control module has connected to the ECC800e, and the infrared
remote control module and ECC800e are powered on.
You have obtained the IP address of the ECC800e as well as the user name and password
used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800e is
prepared, and the PC has connected to port WAN on the ECC800e.
Set the address to 1 by setting the DIP switch on the infrared remote control module.
Table 7-2
describes how to set the DIP switch.
The DIP switch consists of toggle switches 1-5 (from left to right). Toggle switches 1-4
specify the address of the infrared remote control module. Toggle switch 5 specifies the
address of the RS485 build-out resistor. 0 indicates OFF, and 1 indicates ON. The toggle
switch 5 is set to OFF.
Toggle
Switch 1
ON
OFF
The infrared remote control module address is set to 2 by default.
Log in to the ECC800 WebUI as an administrator.
Choose Home > Device Management.
Choose Infrared Remote Control Module from Device type drop-down list box and
select Connect to for ECC800. Then set device parameters, as listed in
By default, an infrared remote control module is connected to port COM2 on the
ECC800. If the infrared remote control module is connected to another port, set the
COM port to the ECC800 port connected to the infrared remote control module.
Copyright © Huawei Technologies Co., Ltd.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
7 Feature Description
Toggle
Switch 4
OFF
OFF
Table
7-3.
163