Commissioning A Door Status Sensor - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Check Method
----End

5.9.6 Commissioning a Door Status Sensor

If a door status sensor is installed, perform the following steps to configure it.
Procedure
Step 1 Set parameters for a door status sensor.
Step 2 Check the door status sensor functions.
Table 5-29 Commissioning the sensor
Check Method
Open the cabinet door.
Issue 06 (2020-01-02)
To use the AI/DI sensor, enable the corresponding AI/DI port and name the sensor. After that, the
specific alarm can be reported.
If the sensor is prefabricated, only check its settings.
Scenario 1: Connect the door status sensor to the AI/DI port on the independent
deployment AI/DI unit (AI/DI_1 is used as an example).
a.
On the WebUI, choose Monitoring > System > Faraway AI/DI Group >
Faraway AI/DI1 > Running Parameters > AI/DI_1 Port Settings, set AI/DI_1
sensor to Enable, and click Submit. Set AI/DI_1 sensor name to Door sensor 1,
check that AI/DI_1 sensor type is set to Door Sensor, and click Submit.
b.
Perform the preceding operations to set parameters for ports AI/DI_2 to AI/DI_8.
Order number of door sensor name is same as cabinet.
Scenario 2: Connect the door status sensor to the AI/DI port on the rack environment unit
(AI/DI_1 is used as an example).
On the WebUI, choose Monitoring > IT Cabinet > IT Cabinet 1 > Cabinet
Collector1 > Running Parameters > AI/DI_1 Port Settings, set AI/DI_1 sensor to
Enable, and click Submit.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
alarm threshold, High humidity alarm threshold,
and Low humidity alarm threshold as required.
NOTE
The default values of High temperature alarm threshold,
Low temperature alarm threshold, High humidity alarm
threshold, and Low humidity alarm threshold are 30.0° C,
5.0° C, 85.0% RH, and 15.0% RH, respectively.
Normal Connection Status
Scenario 1: Door sensor 1 AI/DI_1 DI alarm is
generated on the active alarm page of the app or
WebUI.
Scenario 2: If the Front door open or Rear door open
alarm is enabled, Front door open or Rear door open
5 Power-On Commissioning
129