ECC800 Data Center Controller
User Manual
Prerequisites
The upstream power input circuit breaker of the AC actuator is turned on.
Procedure
Step 1 Set running parameters for the AC actuator.
Table 5-22 Setting AC actuator parameters
Path
Monitoring > Aisle > AC Actuator
Group > AC Actuator > Running
Parameters
Step 2 Check and configure the wireless networking (802.15.4) function of the AC actuator.
Before networking, ensure that the AC actuator has no network parameters, that is, the RF_Z
indicator of AC actuator is steady green. If the RF_Z indicator is not steady green, hold down
the BLINK button for 10 seconds (more than 10 seconds) to enter non-networking status.
1.
2.
3.
4.
Step 3 Check the functions of the AC actuator.
Issue 06 (2020-01-02)
This part describes how to connect the charging cable of the pad to the AC OUT2 port on the AC
actuator.
Hold down the SW button on the ECC800 main control module for 2 seconds (1.2–5
seconds allowed). The RF_Z indicator on the ECC800 main control modules turns from
steady green to blinking green at super short intervals (blinking at 10 Hz, on for 0.05
seconds and then off for 0.05 seconds). The ECC800 enters the wireless networking
(802.15.4) pairing status.
Hold down the BLINK button on the AC actuator for 2 seconds (1–5 seconds allowed).
The RF_Z indicator on the AC actuator turns from steady green to blinking green
intermittently at super short intervals (blinking at super short intervals for 0.5 second and
then off for 0.5 second). The component enters the wireless network search status.
After the wireless networking (802.15.4) pairing succeeds, the RF_Z indicator on the AC
actuator starts to blink at long intervals.
After all AC actuators are networked, hold down the SW button on the ECC800 main
control module for 2 seconds (1.2–5 seconds allowed). The RF_Z indicator on the
ECC800 main control modules turns from blinking green at super short intervals to
blinking green at long intervals (blinking at 0.5 Hz, on for 1 second and then off for 1
second). The ECC800 exits the wireless networking (802.15.4) pairing status.
If two or more ECC800 controllers need to be networked in wireless (802.15.4) mode, only one system
can be networked at one time. During the networking, ensure that the RF_Z indicators on the ECC800
main control modules of other systems are blinking at long intervals or steady on.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Operation
Set Route 2 Control Mode to PAD
Charging, and click Submit. The system
automatically switches on the AC OUT 2
circuit breaker for the AC actuator.