Huawei ECC800 User Manual page 114

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Step 2 Add a PMAC625.
1.
2.
Table 5-9 Adding a PMAC625
Path
Home > Device
Management
3.
4.
----End
Issue 06 (2020-01-02)
Figure 5-8 Communications address of the PMAC625
Ensure that the baud rate of the PMAC625 (the default baud rate is 9600) is consistent with that of the
COM port on the ETH converter.
Log in to the ECC800 WebUI as an administrator.
Follow the instructions in the following table to add the PMAC625.
Item
Device type
Connect to
Communications
port
Device address
Click Connect Test to check whether the PMAC625 connects to the ECC800 properly.
If the PMAC625 connects to the ECC800 properly, click Add Device.
If the PMAC625 does not connect to the ECC800 properly, check whether the cable
between the PMAC625 and the ECC800 is connected properly, whether the
PMAC625 and ECC800 are running properly, and whether the input parameters are
consistent with the PMAC625 parameters.
Choose Monitoring > System > ETH Converter Group > ETH Converter n >
Running Parameters and set Device name to ETH Converter_device position.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select PMAC625 from the drop-down list box.
Select ETH Converter n from the drop-down list
box.
Select COM1/COM2 from the drop-down list box.
In this example, Device address is set to 100.
During actual configurations, set the device address
for the PMAC625 based on the actual situation.
5 Power-On Commissioning
105