Commissioning A Door Status Sensor (Connected To The Ai/Di Port On The Uim20A Expansion Module) - Huawei ECC800-Pro User Manual

Data center controller
Hide thumbs Also See for ECC800-Pro:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Procedure
Step 1 Choose Monitoring > Cabinet > IT Cabinet1 > Cabinet Collector1 > Running
Parameters, set the door status sensor parameters.
Table 6-5 Parameter settings
Setting
area
AI/DI_1
Port
Settings
AI/DI_2
Port
Settings
Step 2 Check the door status sensor functions.
Table 6-6 Function check
Check Method
Close and then open the
door.
----End
6.4.1.3 Commissioning a Door Status Sensor (Connected to the AI/DI Port on
the UIM20A Expansion Module)
If a door status sensor is installed, perform the following steps to configure it.
Context
Procedure
Step 1 Set parameters for a door status sensor.
Issue 02 (2020-09-07)
Object
Method
Front
1. Choose AI/DI_1 sensor to Enable, click Submit.
door
2. Set AI/DI_1 sensor type to Door sensor, click Submit.
status
(AI/DI_1)
Rear
1. Choose AI/DI_2 sensor to Enable, click Submit.
door
2. Set AI/DI_2 sensor type to Door sensor, click Submit.
status
(AI/DI_2)
To use the AI/DI sensor, enable the corresponding AI/DI port and name the
sensor. After that, the specific alarm can be reported.
If the sensor is prefabricated, only check its settings.
If multiple door status sensors are connected, commission one door status
sensor first and then commission the other door status sensors in the same
way.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
If the alarm is enabled for the front and rear
doors, a cabinet door open alarm is displayed on
the active alarm screen of the app or the active
alarm page of the WebUI.
6 Feature Description