ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Path
Step 3 Set SNMP parameters.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10. After setting the parameters, click Confirm.
11. Click Export in the Mib File pane, export the MIB file, and send it to the
----End

6.15 Network Security Management

Choose Monitoring > System > ECC800 > Running Parameters > Unhide All
Advanced Signals > Other Parameters.
Issue 02 (2020-09-07)
Parameter
Default
gateway
Choose System Settings > NMS Application > SNMP.
Set SNMP Version to SNMPv3 and set SNMP port number to the required
port number or retain its default value 161.
Click Submit under SNMP.
Click Add under SNMPv3.
Set User name, set Authentication protocol to SHA or MD5, set Privacy
protocol to AES or DES, and specify MD5/SHA password, Confirm MD5/SHA
password, DES/AES password, and Confirm DES/AES password.
NO TE
– Set User name, MD5/SHA password, and DES/AES password to any character
strings that meet the system requirements. Note that MD5/SHA password and
DES/AES password must be set to different values. Record the settings.
– MD5 and DES are insecure protocols. Therefore, you are advised to set
Authentication protocol to SHA or set Privacy protocol to AES.
Set Password validity period and Advance expiration notification (days).
After setting the parameters, click Confirm.
Click Add under SNMP Trap.
Set Trap target address and Trap port, set SNMP version to SNMPv3, and
specify SNMPv3 user name. Set Trap target address to the IP address of the
NMS server and set Trap port to the port defined by the user.
development engineers of the NMS.
NO TE
For enterprise users: Log in to http://support.huawei.com/enterprise, download the
software package of the required version from Support > Software Download >
Network Energy > Fusion Modular Data Center > ECC800, and decompress the
software package to obtain the MIB file.
For carrier users: Log in to http://support.huawei.com, download the software package
of the required version from Support > Software > Carrier Cloud & Data Center >
Data Center Facility > Fusion Modular Data Center > ECC800, and decompress the
software package to obtain the MIB file.
Copyright © Huawei Technologies Co., Ltd.
Default
Setting
Value
192.168.8.1
Set this parameter based on the
default gateway address assigned by
the network administrator.
6 Feature Description
243