How Can I Set And Add A Uim20A Expansion Module (Modbus-Tcp); How Can I Set And Add A Multi-Functional Sensor - Huawei ECC800-Pro User Manual

Data center controller
Hide thumbs Also See for ECC800-Pro:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
----End

8.1.7.27 How Can I Set and Add a UIM20A Expansion Module (Modbus-TCP)?

Prerequisites
Connect one end of a network cable to the PoE port on the UIM20A expansion
module and the other end to the LAN port on the ECC800-Pro or the PoE port on
the smart ETH gateway.
Context
The UIM20A expansion module supports self-discovery and does not need to set
parameters.
Procedure
Step 1 Set the running parameters and control parameters for the UIM20A expansion
module on the WebUI.
1.
2.
3.
4.
----End

8.1.7.28 How Can I Set and Add a Multi-functional Sensor?

If a multi-functional sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the PoE port on the
multi-functional sensor, and the other end has been connected to the PoE port on
the smart ETH converter.
Procedure
Step 1 Set multi-functional sensor parameters.
On the WebUI, choose Monitoring > Aisle > Multi-Func Sensor Group > Multi-
Func Sensor1 > Running Parameters, ensure that Smoke enable and Temp
enable are set to Enable, set High temperature alarm threshold and other
parameters as required, and then click Submit.
Issue 02 (2020-09-07)
whether the parameter settings are consistent with the independent
deployment AI_DI unit parameters.
NO TE
Cascading of UIM20A expansion modules is not supported.
Log in to the ECC800-Pro WebUI as an administrator.
Choose Monitoring > System > UIM Group > UIMn.
On the Running Parameters tab page, set UIM20A expansion module
running parameters.
On the Controls tab page, set the UIM20A expansion module control
parameters.
Copyright © Huawei Technologies Co., Ltd.
8 FAQ
296

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents