ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Prerequisites for the iCooling Function
Before setting the iCooling function, the following requirements must be met:
WebUI Operations
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 If the iCooling function needs to be used, choose Monitoring > Cooling >
Running Parameters. On the iCooling parameter setting page, set Enable
iCooling to Yes and click Submit to finish the iCooling function setting.
Figure 6-74 Setting the iCooling function
Issue 02 (2020-09-07)
The smart cooling products in each area quickly respond to load changes
in the areas and are regulated to achieve optimal energy efficiency.
Determine the installation position for the cabinet temperature sensor in strict
accordance with the requirements in the installation guide.
After installing the cabinet equipment, use filler panels to seal the vacant U
space.
The smart module plan view has been created. The positions of devices in the
smart module plan view must be the same as their actual locations.
All smart cooling products in the smart module need to be networked for
teamwork. For details about how to configure teamwork networking, see the
smart cooling product user manual of the corresponding model. One smart
module has only one group. In this group, communication between the slave
and master units as well as communication between the master unit and the
ECC800-Pro is normal.
The WebUI displays the Enable iCooling page only for smart cooling products
that support the iCooling function.
The scenario is dual-row cold aisle containment and the following conditions
are met:
Smart cooling product should be placed face to face.
The smart module is configured with an integrated UPS or integrated
PDU. Electricity has been configured for IT cabinets, network cabinets,
and smart cooling products. The ECC800-Pro collects statistics on IT
branch power information, which is mapped to IT cabinets and network
cabinets.
Rack environment units or UIM20A expansion module and cabinet-level
temperature sensors are installed for IT cabinets or network cabinets. The
ECC800-Pro can monitor the temperature of each cabinet.
At least one cold-aisle temperature and humidity sensor is installed for
each smart cooling product, and each smart cooling product can detect
the sensor readings.