FusionDC1000A Prefabricated All-in-One Data
Center
Installation Guide (IT Scenario)
Materials: electric heating belt, tinfoil, thermal insulation foam
Skill requirement: common technician
Procedure
Step 1 Wrap the electric heating belt around the drainpipe and water refill pipe outside
the pre-fab. module.
Figure 8-7 Wrap the electric heating belt around the drainpipe and water refill
pipe
Step 2 Wrap the electric heating belt and pipes with tinfoil.
Step 3 Secure the temperature probe to the pipe using a cable tie.
Issue 01 (2021-04-20)
NO TE
● The drainpipe is pre-integrated with the electric heating belt in the outdoor unit
compartment. The outdoor part is reserved in the outdoor unit compartment and needs
to be routed onsite.
● The water refill pipe needs to be routed onsite.
NO TE
Secure the temperature probe to the position on the water refill and drainage pipe. The
position is the point where the electric heating belt is wrapped 50 cm long around the
water refill and drainage pipe from the water refill and drainage pipe port.
Copyright © Huawei Technologies Co., Ltd.
8 Installing Devices Inside the Pre-fab. Module
73