Order no.
SCCR (short circuit current rating)
Minimum short-circuit current
Current demand of contactors/circuit breakers and fans.
1)
The specified power loss represents the maximum value at 100 % capacity utilization. The value in normal operation is
2)
lower.
The cabinet height increases by 10" (250 mm) with degree of protection IP21, and by 16" (400 mm) with degrees of
3)
protection IP23 (NEMA1 filtered), IP43, and IP54 (NEMA12 ventilated).
The connection is made directly at the circuit-breaker -Q1.
4)
Stripped lengths of the power cables: front 0.71" (18 mm), rear 1.46" (37 mm).
5)
Tightening torque: 31 Nm.
Stripped lengths of the power cables: front 1" (25.4 mm), rear 2" (50.8 mm).
6)
Tightening torque: 42.4 Nm.
Minimum current required for reliable tripping of the contained protective devices.
7)
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
6SL3700-
kA IC
A
7)
0LG32-
0LG34-
8AU3
0AU3
25
25
3000
3500
Cabinet Modules
5.1 Line Connection Modules
0LG36-
0LG38-
3AU3
0AU3
25
35
9000
15000
0LG41-
0AU3
85
9000
149