Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to function, terminal M2 must be connected.
This is achieved through one of the following measures:
1. Provision of the ground reference of the digital inputs.
2. A jumper to terminal M (Note the following: This removes the electrical isolation for these
digital inputs.)
Note
If the 24 V supply is briefly interrupted, then the digital outputs are deactivated during this
time.
8.20.5

X100 - X103 DRIVE-CLiQ interface

Table 8- 22
DRIVE-CLiQ interface X100 – X103
Pin
1
2
3
4
5
6
7
8
A
B
Connector type: RJ45 socket
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Order number: 6SL3066-4CA00-0AA0
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
8.20 K90, Control Unit CU320-2 DP
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronics ground
Options