In contrast to the connection for the clockwise phase sequence, two phases have to be
reversed with a counter-clockwise phase sequence (viewed from the drive shaft).
Note
Direction of motor rotation
If the motor was connected with an incorrect direction of phase rotation, it can be corrected
without replacement of the phase sequence via p1821 (phase rotation direction reversal).
The correct phase sequence must be observed in both sub-cabinets when connecting
cabinet units in parallel, since it is not possible to use converter functions to correct different
phase sequences in the two sub-cabinets at a later stage.
For motors that can be star-connected or delta-connected, it must be ensured that the
windings are interconnected consistent with the operating voltage indicated on the type plate
or in the motor documentation. Make sure that the winding insulation of the connected motor
has sufficient insulation strength to meet the requirements for converter operation.
4.5.7

Line supply connections

Line Connection Modules
The line supply takes place in the Line Connection Module at terminals U1/L1, V1/L2,
W1/L3.
Table 4- 11
Terminals
U1/L1, V1/L2, W1/L3
3 ph. AC power input
Dimensions for connecting alternative cable lugs, see Section "Cable lugs" in the section "Electri-
1)
cal installation".
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
Cabinet and motor connection terminals
Cabinet (motor connection terminals)
U2/T1
V2/T2
W2/T3
Line supply connection, Line Connection Modules
Technical specifications
Voltage:
380 V 3 ph. AC -10% to 480 V 3 ph. AC +10% (-15% < 1 min)
500 V 3 ph. AC -10% to 690 V 3 ph. AC +10% (-15% < 1 min)
Connection:
For frame size FL and GL, the connection is made directly on the
circuit breaker -Q1 (-> see Technical specifications)
For frame size JL, KL, and LL, the connection is made to connec-
tion panel -X1:
M12 / 50 Nm for cable lugs in accordance with DIN 46234 or DIN
46235
1)
Electrical installation
4.5 Connections
Motor (connection terminals)
U
V
W
89