Siemens SINAMICS S120 Device Manual page 67

Cabinet modules nema
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Item
Action
Signal connections
19
Cabinet operation by higher-level controller / control room.
The control cables must be connected in accordance with the interface assignment
and the shield applied.
To prevent interference, the control cables must be routed separately from the power
cables.
Cabling and connections must always comply with the relevant EMC guidelines.
(→ See Chapter "Electrical installation")
20
DRIVE-CLiQ cables
Options
21
G20,
CBC10 Communication
Board
22
G33,
CBE20 Communication
Board
23
G51 to G54,
TM150 Temperature
Sensor Module
24
K01 to K05,
safety license for 1 to 5
axes
25
K46,
SMC10 Sensor Module
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
All DRIVE-CLiQ cables must be connected correctly.
The permissible cable lengths should be carefully ob-
served.
(→ See "S120 Commissioning Manual, Rules for wiring
with DRIVE-CLiQ" 
 )
(→ See "S120 Equipment Manual for Booksize Power
Units, DRIVE-CLiQ Cabinet Gland" and "S120 Equipment
Manual for Booksize Power Units, DRIVE-CLiQ Coupling")
The supplied CBC10 is installed in the factory in the option
slot of the Control Unit.
(→ See Chapter "Options", Section "G20, CBC10 Commu-
nication Board")
The supplied CBE20 is installed in the factory in the option
slot of the Control Unit.
Remove the CBE20 in a de-energized state and note
down the MAC address. Install the CBE20 into the option
slot again.
(→ See Chapter "Options", Section "G33, CBE20 Commu-
nication Board")
A maximum of 12 temperature sensors (PT100, PT1000,
KTY84, PTC, bimetallic NC contact) can be connected to
the TM150 Terminal Module.
(→ See Chapter "Options", Section "G51 to G54, TM150
Temperature Sensor Module")
Activating the safety licenses.
(→ See Chapter "Options", Section "K01 to K05, Safety
license for 1 to 5 axes")
The SMC10 Sensor Module is used for determining the
actual motor speed and the rotor position angle.
The following encoders are supported by the SMC10 Sen-
sor Module:
Resolver, 2-pin
Resolver, multi-pin
(→ See Chapter "Options", Section "K46, SMC10 Sensor
Module for determining the actual motor speed and the
rotor position angle")
Electrical installation
4.2 Checklist for electrical installation
included/completed?
67

Advertisement

Table of Contents
loading