Troubleshooting: Battery Charger Error and Fault Codes
Machine is Inoperative and InfoCenter Power Light Indicates That a Fault Has
Occurred
Possible Causes
System fault has been detected by controller.
An electrical fault occurred that can be reset
by the controller.
Machine Operates But InfoCenter Display is Not Working
Possible Causes
The wire harness connections or wires to the
InfoCenter display are loose or damaged.
The InfoCenter display is damaged.
Use the Faults screen information in the
InfoCenter section of this chapter to help
identify source of problem.
Attempt to restart the machine to see if the
machine operation has returned to normal. If
the fault still remains, use the Faults screen
information in the InfoCenter section of this
chapter to help identify source of problem.
Check the electrical connections. Repair the
wiring as necessary.
Replace the InfoCenter display.
Page 3–10