Preconditions
Feeder earthing switch in CLOSED position
High-voltage door open
In the switching-device compartment and in the voltage transformer compartment:
Low-voltage connector stowed away
Bushing plate and associated bolting material available:
6 bolts M8x20 with contact washers and plain washers
Connecting cables and associated bolting material available:
3 nuts M8 with contact washers and plain washers
Vertical partition and associated bolting material available:
8 bolts M8x20 with contact washers and plain washers
Protection plate and associated bolting material available:
4 nuts M8 with contact washers
Voltage transformer compartment and associated bolting material available:
8 bolts M8x20 with contact washers
Lid of metal cover and associated bolting material available:
2 bolts M8x20 with contact washers
Wiring duct cover and associated bolting material available:
3 bolts M8x20 with contact washers
Procedure
Install the bushing plate with bushings.
Fix the partition (5) by screwing the bolts in all around hand-tight:
6 bolts M8x20 with contact washers and plain washers
Tighten the bolts with torque 25 Nm.
139-2021.9 / 07
Accessing the connection compartment through the front
NOTICE
Damages inside the switching-device compartment
Damages
inside
the
compartment due to incorrect or incomplete installation of the partition / bushing
plate.
To fasten the partition / bushing plate, always assemble all bolted joints all
around, and screw them in up to the end of the thread.
switching-device
compartment / voltage
NXAIR M
transformer
173