Procedure
To open the actuating opening for racking, lift the operating slide as far as it will go and hold
it.
Push the racking crank for moving the withdrawable circuit-breaker onto the operating shaft,
and turn counter-clockwise as far as it will go.
Fig. 373: Lifting the operating slide
Remove the racking crank for moving the withdrawable circuit-breaker.
Depending on the access mode intended, turn the double-bit key until the operating mode
indicator changes to "M" or to "T":
Fig. 375: Turning the key clockwise
Remove the double-bit key.
To close the actuating opening, push the operating slide down as far as it will go.
139-2021.9 / 07
Panels with motor operating mechanism control
To release electrical access to the withdrawable circuit-breaker, change from "H" to
"M" by turning 90° clockwise.
To block any access to the withdrawable circuit-breaker, change from "H" to "T" by
turning 90° counter-clockwise.
from
to
Fig. 374: Turning the racking crank
counter-clockwise
Fig. 376: Turning the key