Siemens NXAIR M Operating Instructions Manual page 72

Air-insulated switchgear
Table of Contents

Advertisement

Operating the circuit-breaker panel
Take the low-voltage connector out of the support located underneath the low-voltage
compartment.
Fig. 120: Low-voltage connector stowed away
Carefully plug on the low-voltage connector (2) from the front.
To secure the low-voltage connector, push the longitudinal fastener (1) of the coupling
downwards.
Fig. 121: Plugging on the low-voltage connector
Close the high-voltage door.
Switch the auxiliary voltage on.
The motor in the circuit-breaker starts up and charges the spring energy store. The position
indicator for the spring energy store in the circuit-breaker changes to CHARGED.
The withdrawable circuit-breaker is inserted in the panel and the high-voltage door is closed.
72
1
3
2
Fig. 122: Locking the low-voltage
NXAIR M
connector
139-2021.9 / 07

Advertisement

Table of Contents
loading

This manual is also suitable for:

139-2021.9

Table of Contents