Opening The Circuit-Breaker Manually - Siemens NXAIR M Operating Instructions Manual

Air-insulated switchgear
Table of Contents

Advertisement

Panels with motor operating mechanism control

23.11 Opening the circuit-breaker manually

Opening the circuit-breaker manually is carried out by pushing a rod through an actuating opening in the
high-voltage door, thereby operating the OFF pushbutton underneath the high-voltage door. This can be
done with the control door either open or closed. When the control door is closed, the push rod is inserted
through an opening in the control door (1). The indicator for the circuit-breaker position can be seen through
an inspection window (2).
Fig. 377: Circuit-breaker type 3AE1:
actuating opening for opening
the circuit-breaker manually
Fig. 379: Circuit-breaker
type 3AE1:
control door
226
1
2
Fig. 380: Circuit-breaker
NOTICE
Conflicting operation
The requirement of setting the panel to either local or remote control prevents
operating the panel locally and centrally at the same time.
For any local operations ─ manual or electrical ─ set the panel to local
control, for example by switching the local-remote switch to LOCAL
position.
Fig. 378: Circuit-breaker type 3AE5:
actuating opening for opening the
circuit-breaker manually
type 3AE5:
control door
NXAIR M
Actuating opening
(1)
for opening the
circuit-breaker
Inspection window
for CLOSED/OPEN
(2)
indicator of the
circuit-breaker
139-2021.9 / 07