Verifying safe isolation from supply

16.7 Verifying safe isolation from supply with the CAPDIS or VOIS device system

Preconditions
High-voltage door closed
Door to low-voltage compartment closed
Indication "Operational high voltage not present" visible

16.8 Supplier information

Further information for the devices to get from:
132
DANGER
Electric shock
Always verify safe isolation from supply without any doubt
If safe isolation from supply is verified erroneously although operational high
voltage is still applied, there is danger to life.
Before performing any kind of checks or work in the busbar compartment
or the connection compartment of each panel, verify safe isolation from
supply in these compartments without any doubt.
Observe the Five Safety Rules.
Safe isolation from supply is verified as soon as L1, L2 and L3 have been
determined to be isolated from supply.
Device
VOIS+ / VOIS-R+ /
CAPDIS-S1+ / CAPDIS-S2+
LRM system
LRM-ST voltage indicator
Supplier:
www.kries.com
www.horstmanngmbh.com
Siemens AG / Order No.: 8DX1620
NXAIR M
139-2021.9 / 07