Taking The Withdrawable Circuit-Breaker Out Of The Panel - Siemens NXAIR M Operating Instructions Manual

Air-insulated switchgear
Table of Contents

Advertisement

10.19 Taking the withdrawable circuit-breaker out of the panel

Preconditions
Service truck available and selected according to the corresponding panel width
Withdrawable circuit-breaker racked to test position
Spring energy store in the circuit-breaker discharged
High-voltage door open
Low-voltage connector stowed away
139-2021.9 / 07
CAUTION
Injury
The mechanism inside a withdrawable circuit-breaker can cause injuries by getting
squeezed, caught or cut.
Do not remove any parts of the covering.
Do not charge the spring energy store in the circuit-breaker.
CAUTION
Heavy weight of withdrawable part
Removing the withdrawable part without service truck can cause injuries.
Do not try to remove the withdrawable part while service truck is not
interlocked with the panel.
Fig. 93: Circuit-breaker panel
with high-voltage door
open
Operating the circuit-breaker panel
Fig. 94: Circuit-breaker panel without
service truck
NXAIR M
59

Advertisement

Table of Contents
loading

This manual is also suitable for:

139-2021.9

Table of Contents