Typical Power Cable Sizes - ABB ACS560 Quick Installation And Start-Up Manual

Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

98 Technical data

Typical power cable sizes

Drive type
ACS560
3-phase U
= 400 V (380...480 V)
N
02A6-4
03A3-4
04A0-4
EN
05A6-4
HI
07A2-4
09A4-4
12A6-4
017A-4
025A-4
033A-4
039A-4
046A-4
062A-4
073A-4
088A-4
106A-4
145A-4
169A-4
206A-4
246A-4
293A-4
1) The cable sizing is based on maximum parallel layout of 6 cables laid on a cable ladder side by side, ambient
temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52/2001). For
other conditions, size the cables according to local safety regulations, appropriate input voltage and the load
current of the drive.
2) Aluminum cables must not be used with frames R0...R4.
3) In the USA, aluminum cables must not be used.
Frame size
Cu cable type
2
mm
R0
3 × 1.5 + 1.5
R0
3 × 1.5 + 1.5
R0
3 × 1.5 + 1.5
R0
3 × 1.5 + 1.5
R0
3 × 1.5 + 1.5
R0
3 × 2.5 + 2.5
R1
3 × 2.5 + 2.55
R2
3 × 2.5 + 2.5
R2
3 × 6 + 6
R3
3 × 10 + 10
R3
3 × 10 + 10
R3
3 × 16 + 16
R4
3 × 25 + 16
R4
3 × 35 + 16
R5
3 × 35 + 16
R5
3 × 50 + 25
R6
3 × 95 + 50
R7
3 × 120 + 70
R7
3 × 150 + 70
R8
2 × (3 × 70 + 35)
R8
2 × (3 × 95 + 50)
IEC 1)
AI cable type 2)
Cu cable type
2
mm
AWG/kcmil
-
-
-
-
-
-
-
-
-
-
-
-
3 × 35
3 × 50
3 × 70
3 × 70
3 × 120
3 × 150
250 MCM
3 × 240
300 MCM
2 × (3 × 95)
2 × 2/0
2 × (3 × 120)
2 × 3/0
US
AI cable type 3)
AWG/kcmil
16
-
16
-
16
-
16
-
16
-
14
-
14
-
14
-
10
-
8
-
8
-
6
-
4
-
2
-
2
-
1/0
-
3/0
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents