Factory Reset; Adding Output Card (4M) - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

10.12 Factory reset

10.13 Adding output card (4M)

A6V10421795_en--_k
4. Enter 'fc360.siemens.com' in the address bar and press <enter>.
 'FC360 Panel Configurator' is open.
5. Click 'Administration'.
6. In the 'Test report' field, click 'Upload to PC'.
7. If prompted, enter a path and a file name and click 'OK'.
 The test report is stored to the PC.
8. Log out of 'FC360 Panel Configurator' and disconnect the PC from the panel.
If a wrong country or language setting was selected during the start-up of the
panel, execute a factory reset to restart.
See chapter 'Restoring factory settings [➙ 106]'.
 Output card (4M) is installed correctly. See chapter 'Output card (4M)
(FCA3602-Z1) [➙ 49]'.
1. Connect the PC to the panel.
2. Open a web browser.
3. Enter 'fc360.siemens.com' in the address bar and press <enter>.
 'FC360 Panel Configurator' is open.
4. Enter access level 3 password to log into access level 3 on the panel.
5. Configure output card (4M). See document
chapter 'Applicable documents [➙ 9]'.
6. Check output card (4M) function.
7. Log out of 'FC360 Panel Configurator' and disconnect the PC from the panel.
Commissioning
Factory reset
A6V10450595
mentioned in
10
119 | 151