8.5.2 Test

8.5.2.1 Detection test
A6V10421795_en--_k
This function sets a zone or device to 'Test' mode. The panel provides two test
modes:
Silent: All alarm devices remain silent in fire alarm condition during testing.
Only the LCD screen displays the test event.
Audible: All alarm devices sound for a period of 10 seconds in fire alarm
condition during testing. The LCD screen displays the test event.
The procedure below indicates how to set a zone to 'Test' mode as an example.
To set a zone to 'Test' mode
1. Press
on the keypad. The 'Main menu' window is open.
Main menu
1 - System status
2 - Operation
3 - Event memory
4 - Login
5 - Lamp test
7 - Logout
2. Select 'Operation' and press
Operation
1 - Isolation
2 - Test
3. Select 'Test' and press
Test
1 - Detection
2 - Lamp test
3 - Voice test
Operations under access level 2
L2
. The 'Operation' window is open.
L2
. The 'Test' window is open.
L2
Operation
8
77 | 151