Device test

11.4 Device test
122 | 151
Smoke detector
1. Enable test mode for the line.
2. Place detector tester RE6 on detector head.
3. Release test gas.
4. Remove detector tester.
5. Confirm the alarm was triggered. Alarm indicator
is flashing.
6. Wait until alarm indicator is off.
7. Set the line to normal mode operation.
Heat detector
1. Enable test mode for the line.
2. Place detector tester RE6T on detector head
and turn on heater.
3. Remove detector tester.
4. Confirm the alarm was triggered. Alarm indicator
is flashing
5. Wait until alarm indicator is off.
6. Set the line to normal mode operation.
Manual call point
1. Enable test mode for the line.
2. Depending on type of call point, insert test key or
open cover to activate.
3. Confirm the alarm was triggered. Alarm indicator
is flashing.
4. Remove test key or close door.
5. Wait until alarm indicator is off.
6. Set the line to normal mode operation.
Upload a test report to PC to check whether all devices on the detector line(s)
have been tested. See Backing up test reports to the PC [➙ 118] for more
information about test report uploading.
Printer
1. Initiate a printer test and check the printout for legibility and correct printing.
2. Check whether the events are correctly printed out.