Maintenance
10
Device test
10.4 Device test
10.5 Completion of work
108 | 124
Building Technologies
Fire safety
Smoke detector
1. Enable test mode for the line.
2. Place detector tester RE6 on detector head.
3. Release test gas.
4. Remove detector tester.
5. Confirm the alarm was triggered. Alarm indicator
is flashing.
6. Wait until alarm indicator is off.
7. Set the line to normal mode operation.
Heat detector
1. Enable test mode for the line.
2. Place detector tester RE6T on detector head
and turn on heater.
3. Remove detector tester.
4. Confirm the alarm was triggered. Alarm indicator
is flashing
5. Wait until alarm indicator is off.
6. Set the line to normal mode operation.
Manual call point
1. Enable test mode for the line.
2. Depending on type of call point, insert test key or
open cover to activate.
3. Confirm the alarm was triggered. Alarm indicator
is flashing.
4. Remove test key or close door.
5. Wait until alarm indicator is off.
6. Set the line to normal mode operation.
Printer
1. Initiate a printer test and check the print out for legibility and correct printing.
2. Check whether the events are correctly printed out.
1. Activate a test alarm through the system operator with remote transmission.
2. Change all 'OFF' status to 'ON'.
3. Have the system owner confirm the revision.
A6V10421795_en--_g
2016-11-18