Advertisement

5.8 Inputs / outputs

Building Technologies
Fire safety
The panel mainboard has four configurable inputs / outputs. Each one can be
configured as an input or output.
The default settings are:
IO1 / IO2: input
IO3 / IO4: output
Figure 12: Connection of configurable IOs
1 Configured as input (Connect to '0V' and IO)
2 Configured as output (Connect to '24V' and IO)
Configured as 'input'
The inputs can be triggered by a potential-free contact. They can be configured as
one of the control functions below:
Mode
class change
Evacuation usage
Reset command
Access level 2
Disable RT Fire and
RT Fault devices
Activate manned
Toggle between
manned/ unmanned
Functionality
Activates all sounder lines and addressable sounders as
long as the input is closed ('Continuous' tone on sounder
lines and 'Tone 1' on addressable sounders).
Activates all the sounder lines and addressable sounders
as long as the input is closed.
The silence / resound functions are available for the
sounder lines and addressable sounders in this state.
Resets the acknowledged alarm events if the input is
closed (only after acknowledge command).
Enables access level 2 as long as the input is closed.
Disables all the RT fire and RT fault devices as long as
the input is closed.
Disabled RT outputs cannot be enabled by the menu
operation.
Switches to 'Manned' mode as long as the input is closed.
Toggles between 'Manned' / 'Unmanned' if the signal
changes on the input.
Installation
5
Inputs / outputs
39 | 124
A6V10421795_en--_g
2016-11-18