Alarm Procedure In Manned Mode - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

Operation
7

Alarm procedure in manned mode

7.2 Alarm procedure in manned mode
66 | 124
Building Technologies
Fire safety
Display provides fire information. See chapter 'Event views [➙ 62]'.
Immediate activation of panel states 'Any Fire'.
In the event of an automatic fire alarm in manned mode, the attendance check
countdown T1 starts if AVC is on.
The Alarm Verification Concept (AVC) for automatic detectors can be deactivated
for special applications. In this case, the alarm procedure follows the description
in chapter Alarm procedure in unmanned mode [➙ 64] (i.e. no attendance check
T1 and no investigation time T2).
During the investigation time, examine the fire location and decide whether it is a
MAJOR INCIDENT or MINOR INCIDENT.
MAJOR INCIDENT: A real fire emergency
Press <Acknowledge>
check.
(Access level 2 password is required.)
→ Buzzer is off.
The investigation time T2 is started.
Optional: Press <Silence/Resound>
silence / resound all sounders.
Read the alarm event information on the LCD and go
to the indicated fire loation.
Activate the nearest manual call point
OR
Press <Alarm Delay Off>
investigation time and activate the panel state
'Global Alarm' innediately.
(Access level 2 password is required.)
→ If configured, RT fire is activated by 'Global
Alarm'.
to confirm attendance
to
to cancel the
A6V10421795_en--_g
2016-11-18