Access Level 2; Isolation - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

7.5 Access level 2

7.5.1 Isolation

Building Technologies
Fire safety
These functions are available with an access level 2 password.
The 'Isolation' function is used to enable / disable section, zone, device, sounders,
RT output, control output.
In certain situations, e.g. maintenance or decoration etc., you can disable parts of a
building to avoid false alarms or fault messages. The 'Isolation' LED is on if the part
of the building is disabled.
WARNING
Disabling system parts render it impossible to acquire and process alarms or
faults!
Fire may spread unhindered.
Deploy staff to monitor the disabled area.
You must enable the disabled area as soon as possible.
The procedure below indicates the steps to disable a section as an example. Refer
to the procedure to enable / disable sections, zones, devices, sounders, RT
outputs, control output.
Disable a section
1. Press
on the keypad, the 'Main menu' window is open.
Main menu
1 - System status
2 - Operation
3 - Event memory
4 - Login
7 - Logout
8 - Query alarm counter
2. Select 'Operation' and press
Operation
1 - Isolation
2 - Test
L2
, the 'Operation' window is open.
L2
Operation
7
Access level 2
71 | 124
A6V10421795_en--_g
2016-11-18