10.3 Function test

Function
Detector line
Outputs
Inputs
Alarm organization
Panel
Building Technologies
Fire safety
The following schedule is recommended for the function test. However, local
regulations have priority.
Activity
Activate all automatic detectors and all manual call points.
Activate a detector or manual call point per line
Check all detectors and manual call points for dirt and check that
usage is in accordance with regulations.
Activate a fault, short circuit and open line, for each line and
check that usage is in accordance with regulations.
Check sounder controls and all acoustic alarm devices.
Activate fire outputs and check the application.
Activate RT alarm and check the RT transmission.
Activate each input and check the application.
Mode Manned.
Activate a detector and manual call point and check the timer V1
and V2 and the RT transmission.
Mode unmanned.
Activate a detector and check the RT transmission.
Check date and time.
Check the display, button and LEDs.
Check earth connections.
Activate mains and battery fault condition and verify the
application.
Maintenance
10
Function test
Interval
(years)
1
2
5
X
X
X
X
X
X
X
X
X
X
X
X
X
X
107 | 124
A6V10421795_en--_g
2016-11-18