5.9 Relay

Building Technologies
Fire safety
The panel mainboard has three relay outputs used for controlling without line
monitoring.
They can be freely configured as:
RT fire
RT fault
Fire control
Fire alarm
The default settings are:
Relay 1: RT fire
Relay 2: RT fault
Relay 3: Fire alarm
Technical:
Current of each relay: max. 2 A @ DC 60 V
Figure 13: Connection of relays
The output "RT fault" is closed (inverse function) in quiescent mode.