4 Options with requirements

EN 54-2
Options with requirements
7.8
Output C to fire alarm devices
according to EN 54-1
7.9.1
Output E to fire alarm routing
equipment
according to EN 54-1
7.9.2
Alarm confirmation input from fire
alarm routing equipment
7.10.1 Outputs G to fire protection equipment
according to EN 54-1
7.11
Delays to outputs
7.12.1 Dependencies on more than one
alarm signal, type A dependency
7.13
Alarm counter
8.3
Fault signals from points
8.8
Output to fault warning routing
equipment
8.9
Output J to fault warning routing
equipment
according to EN 54-1
9.5
Disablement of addressable points
10
Test condition
Building Technologies
Fire safety
The following options with requirements as defined in EN 54-2/A1 are available.
The table below explains how to realize these options in the panel.
The relevant sections according to EN 54-2/A1 are specified in the left column of
the table.
Function in FC361-xx
Installation
Monitored output
Sounder lines
C-NET devices
Monitored output
card (4M)
Input
Monitored output
card (4M)
-
-
-
-
Relay 2
Monitored output
card (4M)
-
-
You will find more information about configuration in document A6V10450595.
1
Options with requirements
Configuration
/ Operation
1
Sounder control
RT fire
RT device confirmation signal;
LED fire brigade activated via
input
Fire output
Alarm Verification Concept;
'Manned' / 'Unmanned'
Type A inhibit time
30...60 sec.
Reset of the first alarm after
90 sec.
Alarm counter
RT fault
RT fault
RT fault
Disable
Test
4
Chapter
5
6
7
5.11.4
5.8
5.11.4
-
-
-
5.11.4
5.5
5.11.4
-
-
25 | 124
A6V10421795_en--_g
2016-11-18