8.5.4 Logging out of the current access level

A6V10421795_en--_k
The 'Logout' function returns to access level 1 from access level 2 or 3.
1. Press
on the keypad. The 'Main menu' window is open.
Main menu
1 - System status
2 - Operation
3 - Event memory
4 - Login
5 - Lamp test
7 - Logout
2. Select 'Logout' and press
Do you want to log out?
Yes (OK) or No (C)
3. Press
to confirm. The panel returns to access level 1.
The panel automatically logs out and returns to access level 1 if no action is taken
within 5 minutes. However, if a digital input on the panel mainboard is used to
enable 'Access level 2', the automatic logout returns to access level 2 from a
higher access level or stays in level 2.
Operations under access level 2
L2
. A confirmation window is open.