Installation
6

Power supply - mains voltage

6.3 Power supply - mains voltage
30 | 151
WARNING
Electrical voltage!
Electric shock
Before connecting the mains voltage ensure that power is not switched on and is
locked to prevent it from being switched on.
1. Insert the mains cable (1) into the housing from the top right side. Use mains
cable with cross section of 3*1.5 mm
2. Insulate the mains cable (1) as needed and connect to the mains fuse
holder (4).
3. Secure the cable with a cable tie.
3
5
Fig. 5: Connection of power supply
1
Mains cable
2
Boundary of mains zone
3
Safety zone (no 230 V power permitted)
4
Mains fuse holder
5
Ground terminal
2
up to 3*2.5 mm
2
.
1
2
N
4