6 Installation
6.1 Instruction
A6V10421795_en--_k
WARNING
Voltage
Electric shock
●
Installation work may only be undertaken by qualified staff and when the
system is de-energized.
NOTICE
Electrostatics
Damage to electronics
●
Suitable protective measures must be taken when working with electronics
modules.
●
Specialist electrical engineering knowledge is required for installation.
●
Only an expert is permitted to carry out installation work.
Incorrect installation can take safety devices out of operation unbeknown to a
layperson.
The installation must comply with all applicable national and local regulations.
●
The panel must be installed in a dry, clean and well vented room.
●
The panel and its components must be protected against dampness and
interfering external influences such as dust, great temperature fluctuations and
mechanical stress.
●
The panel must be installed in a place freely accessible to authorized staff and
the emergency services.
●
The panel must be fitted to a level, non-vibrating wall surface with load bearing
capacity using suitable mounting materials (e.g. screws and plugs).
●
The installation surface and selected wall must be suitable for the weight of the
panel including the batteries used.
●
Installation is not permitted in rooms with high levels of electromagnetic
interference, e.g. in control rooms or right next to power cables and inductive
loads.