Mechanical Data; Environmental Conditions - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

System description
4
Technical data

4.4.3 Mechanical data

4.4.4 Environmental conditions

24 | 151
Batteries
Operating time
Battery capacity
Voltage
Charging current
Load resistance R
imax
1
Each sounder line has an output current of max. 0.5 A. The total output current
of both sounder lines is max. 0.5 A.
2
Each configurable IO on the mainboard has an output current of max. 0.1 A.
The total output current of configurable IOs and aux. power output is
max. 0.2 A.
3
Each output on the output card (4M) has the capability of max. 1.0 A. The total
output current of output card (4M) is max. 2.0 A.
Terminals
Dimensions (W x H x D)
Weight (without batteries) 5.13 kg/5.15 kg
Color
- Housing, Cover
Operating temperature
Storage temperature
Air humidity (no condensation permitted)
Protection category (IEC 60529)
Up to 72 h
2x 12 V, 7 Ah/12 Ah/25 Ah, sealed
lead acid
DC 20.5...28.6 V
Max. 1.6 A
Max. 1 Ω
FC361-ZZ/FC362-ZZ
0.2...2.5 mm
402 x 372 x 132 mm
~RAL 7035, light gray
-5...+40 °C
-20...+60 °C
≤95 % rel.
IP30
FC361-ZA/FC362-ZA
2
402 x 372 x 211 mm
6.32 kg/6.34 kg
A6V10421795_en--_k

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc362 seriesFc361-zzFc361-zaFc362-zzFc362-za

Table of Contents