8.3 Procedure in case of fault

A6V10421795_en--_k
MAJOR INCIDENT: A real fire emergency
MINOR INCIDENT: No fire alarm
The fire alarm reoccurs if any device remains in fire condition.
A fault event is displayed on LCD if a fault occurs.
As an option, the configured outputs can be activated (example, RT fault).
1. Press
on the ↑ PMI.
2. Read message/fault location on the display.
3. Go to the fault location.
4. Eliminate the cause of the fault.
A list of possible faults and solutions can be found in Chapter 'Troubleshooting
[➙ 124]'. Contact your service provider if the fault cannot be eliminated.
The fault is reported again if it is acknowledged but not eliminated.
Procedure in case of fault
Activate the nearest manual call point
OR
Press <Alarm Delay Off>
investigation time and activate the panel state
'Global alarm' immediately.
(Access level 2 password is required.)
→ If configured, RT fire is activated by 'Global
alarm'.
Press <Reset>
to return into normal
operation.
(Access level 2 password is required.)
Check
and ensure that the fire brigade was not
called accidently.