Function overview
7

LED indicators

7.2 LED indicators
60 | 151
FC360
1
2
3
4
5
6
7
8
9
No.
Description
Color
1
Alarm
Red
2
More alarm
Red
3
Fire brigade
Red
4
System on
Green
5
Alarm delay off Yellow
6
Manned or
Yellow
Unmanned
7
General fault
Yellow
8
System fault
Yellow
9
Sounder line
Yellow
and alarm
device fault
10
RT fire fault
Yellow
11
Test condition
Yellow
12
Isolation
Yellow
10
11
12
13 14
Status
Function
On
The panel is in 'Alarm' condition.
Flashing
More than two alarm events happen.
On
Depends on the configuration:
Option 1: Fire brigade was called.
Option 2: RT fire output relay is
activated. Call the fire brigade.
On
The panel is in operation.
Flashing
The panel is in investigation time of
AVC process.
On
The panel is in 'Manned' operation.
Off
The panel is in 'Unmanned' operation.
On
Indicates any fault event in the
system.
On
Indicates CPU failure.
On
All alarm devices are disabled.
Flashing
One or more alarm devices are in
fault.
Sounder circuits are in fault.
On
All RT fire devices are disabled.
Flashing
One or more RT fire devices are in
fault.
On
Indicates one or more devices are in
test mode.
On
Indicates there are isolation events.
15 16