Siemens FC361 Series Technical Manual page 84

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

Operation
8
Operations under access level 2
84 | 151
Compensation value
0 ~ 50
50 ~ 80
80 ~ 120
150
All compensation values are stored in the panel. You can view them one by one on
the local panel or view them all in a PC after uploading. See 'Backing up
compensation values to the PC [➙ 118]' for more information about viewing
compensation values from a PC.
To view compensation values from the panel
1. Press
on the keypad. The 'Main menu' window is open.
Main menu
1 - System status
2 - Operation
3 - Event memory
4 - Login
5 - Lamp test
7 - Logout
2. Select 'Event memory' and press
Event memory
1 - Event log
3 - Compensation Value
3. Select 'Compensation Value' and press
open.
Compensation Value
1 - Show log
4. Select 'Show log' and press
screen.
Device IDs in compensation value logs are only visible under access level 3 or
above.
Indication
The dirt level is within a normal range.
Pay attention to value change.
Detector exchange is recommended.
Exchange the detector.
L2
. The 'Event memory' window is open.
L2
. The 'Compensation Value' window is
L2
. The detailed compensation log appears on the