SERVICE & INSTALLATION MENU

Data just before the latest failure
Contents of Check 2
Press "∨" to go to the next page. Press "∧" to go to the previous page.
Continue from previous page
Temperature Status Display
1
Inlet Air Temperature
2
Outlet Air Temperature
IDU Heat Exchanger Liquid Piping
3
(frozen) Temperature
4
Outdoor Temperature
5
Gas Pipe Temp.
6
Evaporating Temp. at Heating
7
Control Information
8
Compressor temperature
Pressure / Frequency
9
Discharge Pressure
10
Inlet Pressure
11
Control Information
12
Operating Frequency (Hz)
Electronic Expansion Valve
13
IDU Electronic Expansion Valve (%)
14
ODU Electronic Expansion Valve1 (%)
Current Value (reference)
15
Compressor Current (A)
86
PMML0565 rev.1 - 04/2022
q1
23
q2
50
q3
25
q4
12
q5
25
q6
03
q7
--
q8
45
q9
18
qA
04
qb
44
qC
44
qd
20
qE
99
qF
20
Corresponds to item "b2" in Check 1.
Corresponds to item "b3" in Check 1.
Corresponds to item "b4" in Check 1.
Corresponds to item "b6" in Check 1.
Corresponds to item "b7" in Check 1.
Corresponds to item "b8" in Check 1.
Corresponds to item "b9" in Check 1.
Corresponds to item "bA" in Check 1.
Corresponds to item "H1" in Check 1. Unit is (×0.1MPa).
Corresponds to item "H2" in Check 1. Unit is (×0.1MPa).
Corresponds to item "H3" in Check 1.
Corresponds to item "H4" in Check 1.
Corresponds to item "L1" in Check 1.
Corresponds to item "L2" in Check 1.
Corresponds to item "P1" in Check 1.