Advertisement

SERVICE & INSTALLATION MENU

6.3.4 Check PCB of the Units

This function is used to Self check the PCB of the indoor and
outdoor units.
1 Select "Check PCB of the Units" on the "Check Menu"
screen and press "OK".
2 Press " ", " ", " ", or " " to select the indoor unit. Press "OK".
If there is only one indoor unit connected to the wired remote
controller, this screen is not displayed (the screen in Step3 is
shown).
3 Check result is shown.
88
PMML0565 rev.1 - 04/2022

Unit check result
Indoor Unit PCB
00
Normal
01
Abnormality of inlet air temperature thermistor
02
Abnormality of outlet air temperature thermistor
03
Abnormality of liquid temperature thermistor
04
Abnormality of remote thermistor
05
Abnormality of gas pipe temperature thermistor
07
Abnormality of transmission of outdoor unit
08
Abnormality of transmission of central station
0A
Abnormality of EEPROM
0b
Zero Cross input Failure
Abnormality of transmission of Indoor unit during check
EE
(Wired remote controller ↔ Indoor unit)
Outdoor Unit PCB
00
Normal
F4
ITO Input failure
F5
PSH Input failure
F6
Abnormality of protection signal detection circuit
F7
Abnormality of phase detection
F8
Abnormality of transmission of inverter
FA
Abnormality of high pressure sensor
Abnormality of compressor discharge gas temperature
Fb
thermistor
FC
Abnormality of low pressure sensor
Fd
Abnormality of evaporating temperature thermistor at heating
Depending on the outdoor unit model:
FE
Abnormality of gas piping temperature thermistor
Abnormality of condensing temperature (heat exchanger)
FF
Abnormality of ambient air temperature thermistor