LIST OF ERROR CODES
This chapter lists the error codes, error details and causes, and action for the errors occur in the processing for data
communication between the CC-Link IE TSN Plus module and slave stations or caused by processing requests from the CPU
module on the own station.
The following table lists the error codes for the CC-Link IE TSN Plus module.
Type

Error codes when a module error occurs

Error codes for I/O signal processing
Error codes when a connection error occurs
Error codes for the message communication function (client)
Error codes for the tag communication function (server)
19.1
Error Codes When a Module Error Occurs
Error codes are displayed in the [Error Information] tab in the "Module Diagnostics" window of the CC-Link IE TSN Plus
module. ( Page 369 Error Information)
Error codes when using CC-Link IE TSN communications and
Ethernet communications
Error
Error definition and causes
code
1080H
The number of writes to the flash ROM has
exceeded 100000.
1124H
• The default gateway is not set correctly.
• The gateway IP address is not set
correctly.
• The default gateway/gateway IP
address (network address after the
subnet mask) is different from that of the
IP address of the own node.
1128H
The port number is incorrect.
1152H
The IP address is not set correctly.
1155H
• The specified connection was already
closed in TCP/IP communications.
• Open processing is not performed.
1167H
Unsent data found, but could not be sent.
19 LIST OF ERROR CODES
404
19.1 Error Codes When a Module Error Occurs
Reference
Page 404 Error codes when using CC-Link IE TSN communications and
Ethernet communications
Page 433 Error codes when using EtherNet/IP communications
Page 434 Error Codes for I/O Signal Processing
Page 435 Error Codes When a Connection Error Occurs
Page 441 Error Codes for the Message Communication Function (Client)
Page 443 Error Codes for the Tag Communication Function (Server)
Action
Replace the module.
• Correct the default gateway IP address.
• Set the same network address as that of the IP address.
Correct the port number.
Correct the IP addresses.
• Perform the open processing for the specified connection.
• Check if the open processing has been performed in the external device.
• Check the settings for connection with the external device.
• Check the operation of the external device or switching hub.
• Since there may be congestion of packets on the line, send data after a
certain period of time.
• Check if the Ethernet cable is connected properly.
• Check that there is no connection failure with the switching hub.
• Execute the communication test, and if the test was completed with an
error, take corrective action.
Detailed
information 1
Detailed
information 2
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
■
■Parameter
information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
■