Communication Period Setting
Set the basic cycle setting and multiple cycle setting.
• Basic cycle setting requires calculation of the communication cycle interval and cyclic transmission time. ( Page 526
Communication cycle intervals)
• Multiple cycle setting is used when communication cycles coexist. ( Page 166 Communication cycles coexistence)
Item
Basic Period
Setting in Units of 1s
Setting
Communication Period Interval Setting (Do
Not Set it in Units of 1s)
Communication Period Interval Setting (Set
it in Units of 1s)
System Reservation Time
Cyclic Transmission Time
Transient Transmission Time
Multiple
Normal-Speed
Period Setting
Low-Speed
*1 To use the CC-Link IE TSN network synchronous communication function, set the same value as the value set in "Fixed Scan Interval
Setting" of "Fixed Scan Interval Setting of Inter-module Synchronization" under "Inter-module Synchronization Setting" in the "Inter-
module Synchronization Setting" tab of "System Parameter".
• When the TSN hub is used, set the timeslot information from the setting values in "Basic Period Setting".
The timeslot information can be checked with the buffer memory. ( Page 469 Timeslot information)
• Set "Communication Period Setting" according to the communication cycle supported by the slave stations.
8 PARAMETER SETTINGS
80
8.1 Parameter Settings for CC-Link IE TSN
Description
Select whether to set the basic cycle in increments of 1s.
Select the setting range of the communication cycle interval.
*1
Enter a value of the communication cycle interval.
*1
Necessary time for the system to guarantee the
communication cycle interval.
When "Communication Speed" of the master station is set to
100Mbps, select 200s.
Set the time to be allocated to cyclic transmission in
communication cycle intervals.
The value of "Communication Period Interval Setting" minus
"Cyclic Transmission Time" and "System Reservation Time"
is displayed.
Select the "Normal-Speed" cycle for a basic cycle.
Setting is not required and can be left as "4".
Select the "Low-Speed" cycle for a basic cycle.
Setting range
• Set
• Not set
(Default: Not set)
• 125.00s
• 250.00s
• 500.00s
• 1000.00s
• 2000.00s
• 4000.00s
• 8000.00s
(Default: 1000.00s)
125.00s to 10000.00s (in
increments of 1s)
(Default: 1000.00s)
• 20.00s
• 200.00s
(Default: 20.00s)
5.00s to 9966.00s (in
increments of 1s)
(Default: 500.00s)
14.00s to 9975.00s (in
increments of 1s)
(Default: 480.00s)
Fixed to 4
• 16
• 32
• 64
• 128
(Default: 16)