Menu Path
Parameter
Ext Inp X62 U/I
Params & Display>
Load Controller>
Ext MinSetpoint
Configuration
Ext MaxSetpoint
Params & Display>
OutValueSelection
Load Controller>
Configuration>
AnalogOutput
CurrMode 0/4mA
LMV5 QSG Rev 4
U = User
O = OEM
S = Service
Configuration of INPUT terminals X62. This input can be configured for 4 to 20mA, 0 to 20mA, 2 to 10VDC,
or 0 to 10VDC. This terminal is usually used for remote setpoint or remote modulation. This input signal is
scaled by parameter Mrange TempSense or Mrange PressSens. NOTE : The limits on this terminal are 3mA
to 21mA, 10.5 VDC. Signals not in this range will cause a alarm.
Establishes the minimum external setpoint that can be input via terminals X62.
Range = 0 to 100% Def = 0 Typ = 10
Establishes the maximum external setpoint that can be input via terminals X62.
Range = 0 to 100% Def = 60 Typ = 100
This selects the process value associated with analog output X63. The selected process value will be
transmitted from X63 with either a 0 to 20mA or a 4 to 20mA signal. The choices for this output are:
1) Load - The current load of the burner using 4-20mA. Parameters CurrMode 0/4mA ,Scale 20mA and
S
Scale 0/4mA have no effect on this choice.
2) Load 0 - The currnet load of the burner using 4-20mA or 0-20mA.
)
3) O2 - The percent O2 curenntly read by the stack O2 sensor.
4) Pos Air - The current position of the air actuator in angular degrees.
5) Pos Fuel - The current position of the fuel actuator in angular degrees.
6) Pos Aux 1 - The current position of the Aux 1 actuator in angular degrees.
7) Pos Aux 2 - The current position of the Aux 2 actuator in angular degrees.
8) Pos Aux 3 - The current position of the Aux 3 actuator in angular degrees.
9) Speed VSD - The current speed of the VSD motor in percent.
10) Flame - The current raw flame signal
11) TempPT1000 - The temperature read by the PT1000 sensor on terminal X60.
12) TempNi1000 - The temperature read by the Ni1000 sensor on terminal X60.
13) TempPt100 - The termperature read by the PT100 sensor on terminal X60.
14) Temp X61 - The tempearture read by the temperature transducer on terminal X61
15) Press X61 - The pressure read by the pressure transducer on terminal X61.
Selects the output signal to be either a 0 to 20mA signal or a 4 to 20mA signal.
Range = 0 to 20mA or 4 to 20mA Def = 0 to 20mA Typ = 4 to 20mA
Sec 4 Pg 48
Descriptions / Notes
g
All
60-
62
All
www.scccombustion.com