Menu Path
Parameter
IgnitionPosGas or
IgnitionPosOil
IgnitionPosAir
Params & Display>
RatioControl>
IgnitionPosAux1
Gas/Oil Settings>
Special Positions>
IgnitionPosAux2
IgnitionPos
IgnitionPosAux3
IgnitionPosVSD
PostpurgePosGas or
PostpurgePosOil
PostpurgePosAir
Params & Display>
PostpurgePosAux1
RatioControl>
Gas/Oil Settings>
Special Positions>
PostpurgePosAux2
PostpurgePos
PostpurgePosAux3
PostpurgePosVSD
Params & Display>
RatioControl>
ProgramStop
Gas/Oil Settings>
Special Positions
LMV5 QSG Rev 4
U = User
O = OEM
S = Service
Sets ignition position of the fuel actuator(s). If one fuel actuator is connected to both the gas and oil valve, it
can still have independent ignition positions for gas and oil. Setting is independent low fire. Range = 0º - 90º
Def = XXXX (not set) Typ = 3º.
Sets ignition position of the air actuator. Setting is independent of the low fire position.
Range = 0º - 90º Def = XXXX (not set) Typ = 5º.
Sets ignition position of the aux1 actuator. Setting is independent of the low fire position.
Range = 0º - 90º Def = XXXX (not set) Typ = 5º.
Sets ignition position of the aux2 actuator. Setting is independent of the low fire position.
Range = 0º - 90º Def = XXXX (not set) Typ = 5º.
Sets ignition position of the aux3 actuator. Setting is independent of the low fire position.
Range = 0º - 90º Def = XXXX (not set) Typ = 5º.
Sets ignition position of the VSD. Setting is independent of the low fire position.
Range = 0 to 100% Def = XXXX (not set) Typ = 50%
Sets the postpurge position of the fuel actuator(s).
Range = 0º - 90º Def = 15 deg Typ = 5º.
S
Sets the postpurge position of the air actuator.
Range = 0º - 90º Def = 15 deg Typ = 30º.
Sets the postpurge position of the aux1 actuator.
Range = 0º - 90º Def = 25 deg Typ = 25º.
Sets the postpurge position of the aux2 actuator.
Range = 0º - 90º Def = 25 deg Typ = 25º.
Sets the postpurge position of the aux3 actuator.
Range = 0º - 90º Def = 25 deg Typ = 25º.
Sets the postpurge position of the VSD.
Range = 0 to 100% Def = 50% Typ = 50%
For gas or oil firing, this parameter will stop the sequence in the selected phase.
This is useful for service work, such as; adjusting pilots, measuring prepurge, etc.
The LMV can be held (program stopped) in the following phases:
24 prepurge, 32 Prepurge FGR, 36 Ignition position, 44 Interval 1 (pilot stabilization), 52 Interval 2 (Main
flame Stabilization), 72 Postpurge position, 76 Postpurge FGR Def = deactivated Typ = deactivated (for
normal operation)
Sec 4 Pg 35