Download Print this page

Siemens LMV5 Quick Start Manual page 156

Hide thumbs Also See for LMV5:

Advertisement

Error
Diag.
Device
Display
code
code
Any #
Fault Feedback
01
86
LMV5
Load Controller
02
03
Any #
01
Fault Feedback
87
AZL5
02
03
Any #
All
Fault Feedback
01
Air Act.
Actuator
Fault Feedback
02
LMV5
Load Controller
88
Fault Feedback
03
AZL5
VSD
Fault Feedback
04
module
VSD Module
Fault Feedback
05
O2 Mod.
O2 Module
Aux 3
Fault Feedback
90
Act.
Aux Actuator 3
Fault Feedback
91
Air Act.
Air Actuator
Gas / Oil
Fault Feedback
Any #
92
Act.
Gas (Oil) Actuator
Fault Feedback
93
Oil Act.
Oil Actuator
Aux 3
Fault Feedback
94
Act.
Aux Actuator 1
LMV5 QSG Rev 4
Meaning for the LMV5x system
Fault with Base Unit (LMV5) or AZL5
Basic unit has detected wrong state of the internal load
controller
CRC error
Key error main loop counter
No feedback for max. number
Basic unit has detected wrong state of the AZL...
CRC error
AZL
Key error main loop counter
No feedback for max. number
Plausibility fault NMT
Undefined fault class of SA
Undefined fault class of LC
Undefined fault class of AZL
AZL
Undefined fault class of VSD module
Undefined fault class of O2 module
Fault with Connected actuators
Basic unit has detected a ROM-CRC error
on the air actuator when checking its feedback signal
Basic unit has detected a ROM-CRC error
on the air actuator when checking its feedback signal
Basic unit has detected a ROM-CRC error
on the gas actuator when checking its feedback signal
Basic unit has detected a ROM-CRC error
on the oil actuator when checking its feedback signal
Basic unit has detected a ROM-CRC error
on the auxiliary actuator when checking its feedback signal
Sec 5 Pg 30
Corrective action
If fault occurs sporadically improve EMC. If fault occurs
continously, replace LMV5
1) Check CANBus cabling. Ensure that all cable shields
(screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and at
the LMV5
2) Check each CANBus Connector to ensure proper
termination (no conductors exposed on the back of the
plug)
3) If fault occurs sporadically: Improve EMC.
4) Replace AZL5...
If fault occurs constantly: Replace defective AZL5...(see
diagnostic code) or basic unit
1) Check CANBus cabling. Ensure that all cable shields
(screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and at
the LMV5x...
2) Check each CANBus Connector to ensure proper
termination (no conductors exposed on the back of the
plug)
3) If fault occurs sporadically: Improve EMC.
4) If fault occurs constantly: Replace actuator according
to diagnostic code.
www.scccombustion.com