11) Change the burner ID on the LMV5 to match the burner ID contained in the .par file.
This can be done via the ACS450 or though the AZL5 directly. The OEM password is
required to do this with either method.
a. If using the ACS450 – Once connected at the OEM level, go to the System LMV5x
dropdown menu. The path is Operation > Burner ID. Change the Burner ID in the
dropdown menu.
b. If using the AZL5 - Disconnect the PC. Once disconnected, the path through the
AZL5 is Updating > Burner ID. A prompt will appear for the password when
Updating is selected on the AZL5.
12) Reset and then initialize the LMV5 using the ACS450.
a. Connect to the LMV5 with the ACS450 at the Service or OEM level. After connecting
successfully, go to the System LMV5x dropdown menu and select Reset BU. A reset
window will appear that states the burner ID and fuel train will be deleted.
b. Click Reset, and the LMV5 will be reset (burner ID and fuel train). An alarm window
will immediately appear that states No Fuel Train Defined. This alarm window does
not need to be closed. The alarm window can be moved out of the way. Click on
Close to close the reset window.
c. The burner ID and fuel train are now erased. Go under the System LMV5x dropdown
menu and select Disconnect. A window will appear that asks Do you want to store
parameters for offline mode?. Click No if a backup (.mdb file) file is not necessary. If
Yes is clicked, the ACS450 will create an .mdb file. The .mdb file creation can take
up to 10 minutes. Creating an .mdb file is discussed in section 9-3.
d. Next, go to the System LMV5x dropdown menu and select Init BU. A window will
appear and the ACS450 will begin reading the parameters. This will take a few
minutes. After this is complete, a window will appear that asks for a .par file. Select
the .par file that contains the parameters set to be uploaded. This parameter set
(.par) will overwrite the parameter set on the LMV5 and will determine the
behavior of the LMV5. Be sure that the correct .par file is selected.
13) A window titled Restore PC > LMV will appear. The message at the bottom of the
window should state New base unit (if burner ID was previously erased by Reset BU) or
Burner ID ok if the burner ID matches. Click on Store in LMV. This will start the upload
process.
14) The messages should appear on the Restore PC > LMV window. These messages are
(in order): Function Succeeded, Transferring Parameters, Status =1, Status = 2, Status =
3, Parameter Transfer Succeeded. The upload process my take up to five minutes to
complete. Also, an alarm may occur during the upload. This alarm is normal, and is to
alert the technician that the new parameter set has been uploaded to the LMV5.
15) Once the Parameter Transfer Succeeded message is shown on the Restore PC > LMV
window, click on Close. The alarm resulting from the upload can also be reset at this
time. The upload is now complete.
LMV5 QSG Rev 4
Sec 9 Pg 5